Kami adalah agen tunggal untuk alat industri merk Kansai Automation dari Jepang dan Cambridge Sensotec Gas Analyzer dari Inggris. Selain itu, kami adalah importir umum semua alat industri disesuaikan dengan kebutuhan end user. Hubungi kami di syukur1970@gmail.com
Penayangan bulan lalu
Minggu, 26 April 2020
yokogawa Duplexed Field Control Unit AFV30D-A41262
n GENERAL
This GS covers the hardware specifications of the
Field Control Unit (FCU) which is the core of the
control function of the Field Control Station (FCS).
n STANDARD SPECIFICATIONS
For the installation specifications and the environmental
conditions common to the systems, refer to “Integrated
Production Control System CENTUM VP System
Overview” (GS 33J01A10-01EN).
l Memory Protection During Power Failure
Battery
Battery Back-up for Main Memory: Max. 72 hours
Battery Recharge Time: Min. 48 hours
l READY Contact Output
2 terminals (NC, C)
Contact Points open during FCU failure
Contact Rating: 30 V DC, max. 0.3 A
Note: When option code /HKU is specified, a FCU fault
contact is output from the House Keeping Unit
(HKU).
l Communication Interface
Vnet/IP Interface: Dual-redundant
For more details, refer to "Integrated Prodction
Control Systrm CENTUM VP System Overview" (GS
33J01A10-01EN)
l HKU Interface (Option)
When option code /HKU is specified, a FCU
fault contact is output from the HKU. Also, the
environmental conditions of the cabinet connected via
the HK bus and optical ESB bus can be monitored and
the operating status of the HKU can be displayed on
the HIS. System alarms can also be displayed.
l No. of Node Units Connectable
Max. 13/FCU
The total number of ESB Bus Node Units (ANB10)
and Optical ESB Bus Node Units (ANB11) that can
be connected to FCU are 13 or less.
l Module Configuration
Power Supply Module (PW481, PW482, or PW484):
2 modules for dual-redundant
configuration.
Processor Module (CP471 or CP461):
2 modules for dual-redundant
configuration.
A dual-redundant configuration is enabled
by using 2 identical modules with same
model code (CP471 or CP461).
I/O Module (*1): Max. 8
*1: Non-standard component.
[19-inch Rack Mountable Type FCU]
l Installation Restrictions
To connect the ESB Bus Node Unit (ANB10) or
Optical ESB Bus Node Unit (ANB11) to the FCU,
install the ESB Bus Coupler Module (EC401 or EC402)
in slots 7 and 8 of the FCU. For the dual-redundant
configuration of the processor modules, EC401 or
EC402 must be installed in both slot 7 and slot 8.
In case ESB Bus has a single configuration, EC401
or EC402 must be installed in slot 7 and keep slot 8
empty.
To install the optical ESB bus node unit and ESB bus
node unit in a remote location, use the Optical ESB
Bus Repeater Master Module (ANT401 or ANT411) to
connect them with an optical fiber cable. To install the
optical ESB bus repeater master module in the FCU,
install a pair of modules in slots 1 to 6 in order from
right to left according to the number of branches. In a
single configuration, install the individual modules in
slots 1, 3, and 5 in order from right to left. For details,
see the “Optical ESB Bus Repeater Module”
(GS 33J60F51-01EN/GS 33J60F52-01EN).
For the limitations and precautions for installing I/O
modules, see “FIO System Overview”
(GS 33J60A10-01EN).
l Power Supply
Specify with the Suffix Code.
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
[Release 6]
F01E.ai